第32卷第14期电网技术Vol.32No.142008年7月PowerSystemTechnologyJul.2008:1000-3673(200814-0019-06:TM852文献标识码:A学科代码:470·40输电线路绝缘子串防冰闪措施研究蒋兴良1,卢杰1,苑吉河2,罗利云3,张志劲1(1.输配电装备及系统安全与新技术国家重点实验室(重庆大学,重庆市沙坪坝区400044;2.南岸供电局,重庆市南岸区400060;3.江西省电力公司超高压分公司,江西省南昌市330006StudyonMeasurestoPreventIcingFlashoverofInsulationStrings激ANGXing-liang1,LU激e1,YUAN激-he2,LUOLi-yun3,ZHANGZhi-激n1(1.StateKeyLaboratoryofPowerTransmissionEquipmentSystemSecurityandNewTechnology(ChongqingUniversity,ShapingbaDistrict,Chongqing400044,China;2.Nan’anPowerSupplyBureau,Nan’anDistrict,Chongqing400060,China;3.ExtraHighVoltageBranch,激angxiElectricPowerCorporation,Nanchang330006,激angxiProvince,ChinaABSTRACT:InJanuaryandFebruary2008,seriousicedisasterbroughttremendouslosstosomeregionalpowernetworksinSouthernandCentralChina.Theicingflashoverofinsulatorstingsisoneoftheprincipalfactorscausingthisicedisaster,thusthepreventionoficingflashoverofinsulatorstringsissignificantforthesecureoperationoftransmissionlineslocatedinice-coveredregions.Throughtheanalysisonicingflashoverofinsulatorstrings,thepapercomparesthecharacteristicofmeasurestopreventicingflashoverofinsulatorstringsoftransmissionlines,pointoutthatthemainreasonscausingicingflashoverofinsulatorstringsaretheaberrationofvoltagedistributionalonginsulatorstringandthecontinuoushighconductivewaterfilmthatappearswhilethebridgediceiciclesaremolten.Moreover,itisalsopointedoutthatinsomemeasurestopreventicingflashover,thePRTVcoating(permanentroomtemperaturevulcanizedanti-contaminationflashovercompositecoatingcannoteffectivelypreventicecoatingoninsulatorsurface,meanwhile,PRTVcoatingmayreducetheicingflashovervoltageofinsulators,thusitisnotrecommendedtousePRTVcoatingtopreventicingflashover.TheV-typeinsulatorstringandtheinsulatorstringcomposedbyinsulatorswithlargerandsmallersheddiametersalternativelycaneffectivelyincreasetheicingflashovervoltageofinsulatorstrings,sotheyarepracticableapproachesforthedesignandrenovationoftransmissionlinesinice-coveredregions.KEYWORDS:transmissionlines;icingandsnowingdisaster;insulatorstrings;ice-coating;flashover摘要:2008年1—2月,南方地区严重的冰灾事故给部分地区电网造成了巨大的损失,绝缘子串冰闪是造成这次冰灾事故的主要因素之一,因此预防绝缘子冰闪对于保证覆冰地区输电线路安全运行十分重要。通过对绝缘子冰闪机理进行分析,文章比较了3种预防输电线路绝缘子串冰闪措施的特点,指出绝缘子串发生冰闪的主要原因是绝缘子串电压分布畸变和冰凌桥接导致融冰时形成了连续高电导水膜,并指出在一些防冰闪措施中,防污闪复合涂料(permanentroomtemperaturevulcanizedanti-contaminationflashovercompositecoating,PRTV并不能有效防止绝缘子覆冰,且会降低绝缘子冰闪电压,因此笔者不推荐采用PRTV预防冰闪。同时,因V型串和间插方式可有效调高绝缘子冰闪电压,这种方式在覆冰地区输电线路设计和改造中较实用。关键词:输电线路;冰雪灾害;绝缘子;覆冰;闪络0引言我国是世界上输电线路覆冰最严重的国家之一。自1954年有输电线路冰灾事故记录以来,1974~1976年、1984年、2005年、2008年相继发生了全国范围内的大面积冰灾事故,2008年1—2月华中、华东、西南等地区五十年一遇的大暴雪、冻雨天气造成了河南、湖南、湖北、江西、四川、重庆、浙江、安徽、广西、贵州和云南等电网输电线路和杆塔大面积覆冰,输变电设施受损严重,给国民经济和人民生活造成了严重影响[1-2]。严重的覆冰不仅会导致输电线路导线和杆塔损毁,也会导致导线对地线、导线对导线的短路以及绝缘子闪络等电气...